63
935.3 "Priority, DHW heating, heating circuit 3"
Setting
Explanations
Priority of DHW heating over heating circuit pump and
mixer
OFF
0
Without DHW heating priority
DHW
1
With DHW heating priority
935.5 "Differential temperature, heating circuit 3"
Setting
Explanations
The flow temperature of the heat generator is higher
than the flow temperature of the heating circuit with
mixer by an adjustable differential temperature. See
also chapter "Function description".
8 K
8
Differential temperature in delivered condition 8 K
0 to 20
Differential temperature adjustable from 0 to 20 K
935.6 "Operating mode, heating circuit 3"
Setting
Explanations
See also parameter 935.7
Heating mode:
Weather-compensated without room tem-
perature hook-up
0
Weather-compensated
without
room temperature in-
fluence
Weather-compensated with room tempera-
ture hook-up
1
Weather-compensated
with
room temperature influ-
ence
935.7 "Room influence factor, heating circuit 3"
Setting
Explanations
The higher the value, the greater the influence of the
room temperature on the set flow temperature of the
heating circuit (heating curve). Operation with room
temperature hook-up must be set for the heating cir-
cuit (parameter 935.6). Change value for heating cir-
cuit with mixer only.
For a sample calculation, see chapter "Heating curve"
in the "Function description"
8
Room influence factor
0 to 64
Room influence adjustable from 0 to 64
1102.0 "Min. speed of speed-controlled primary/heating circuit pump in standard mode, heating circuit 1"
Setting
Explanations
Minimum speed of the internal circulation pump in
heating mode with standard room temperature
...
Delivered condition specified by settings specific to
the heat generator
0 to 100
Minimum speed adjustable from 0 to 100 %
1102.1 "Max. speed of speed-controlled primary/heating circuit pump in standard mode, heating circuit 1"
Setting
Explanations
Maximum speed of the internal circulation pump in
heating mode with standard room temperature
...
Delivered condition specified by settings specific to
the heat generator
0 to 100
Maximum speed adjustable from 0 to 100 %
System configuration (parameters)
Heating circuit 1, Heating circuit 2, Heating…
(cont.)
6130884
Parameter