58
522.3 "Interval until the next service"
Setting
Explanations
Interval until the next service
0
No interval selected
1
3 months
2
6 months
3
12 months
4
18 months
5
24 months
1411.0 "Clear maintenance messages"
Setting
Explanations
Clear maintenance messages once maintenance has
been performed.
No
0
Maintenance messages are active (if present).
Yes
1
Clear maintenance messages once.
596.0 "Maximum heating output"
Setting
Explanations
A limit can be set on the maximum heating output for
heating mode.
100
Heating output in the delivered condition 100 %
0 to 100
Adjustable from 0 to 100 %
597.0 "Limit, max. heating output for DHW heating"
Setting
Explanations
A limit can be set on the maximum heating output for
DHW heating.
100
Heating output in the delivered condition 100 %
0 to 100
Adjustable from 0 to 100 %
1100.2 "Set speed of the primary circuit pump in heating mode"
Setting
Explanations
Set speed of internal circulation pump
■
In heating mode
■
With external demand
■
With demand in conjunction with a low loss header
...
Delivered condition specified by settings specific to
the appliance
20 to 100
Set speed adjustable from 20 to 100 %
1432.1 "Residual head control of primary circuit pump"
Setting
Explanations
Residual head limit value for reducing pump speed of
the internal circulation pump, in mbar
0
Internal circulation pump is controlled in line with the
outside temperature
1 to 255
Internal circulation pump is operated with constant re-
sidual head.
Recommended setting: 120 mbar
1 step
≙
1 mbar
System configuration (parameters)
Boiler
(cont.)
6130884
Parameter