Vitodens 200-W B2HA 112, 150 Service
43
5683 710 - 09
Coding 1
Solar
Select “Solar”
Note:
The solar group is only displayed if a solar control module, type SM1, is connected.
Coding
Coding in the factory setting
Possible change
Speed control solar circuit pump
02:0
Solar circuit pump is not
speed-controlled.
02:1
Solar circuit pump is speed-
controlled with wave packet
control.
02:2
Solar circuit pump is speed-
controlled with PWM control.
DHW tank maximum temperature
08:60
The solar circuit pump is
switched off when the
actual DHW tank
temperature reaches
140°F (60°C) (maximum
DHW tank temperature).
08:10
to
08:90
Set DHW temperature adjustable
from 50 to 194°F (10 to 90°C).
Stagnation time reduction
0A:5
To protect the system
components and heat
transfer medium, the speed
of the solar circuit pump is
reduced when the differential
between the actual DHW
tank temperature and the set
DHW tank temperature is
less than 5 K.
0A:0
Stagnation time reduction
disabled.
0A:1
to
0A:40
Temperature differential adjustable
from 1 to 40 K.
Flow rate solar circuit
0F:70
Solar circuit flow rate at
the maximum pump speed
7 L/minute.
0F:1
to
0F:255
Flow rate adjustable from
0.1 to 25.5 L/minute;
1 step
≙
0.1 L/minute.
Extended solar control functions
20:0
No extended control
function enabled.
20:1
Additional function for DHW
heating.
20:2
Differential temperature control 2.
20:3
Differential temperature control 2
and auxiliary function.
20:4
Differential temperature control 2
for central heating backup.
20:5
Thermostat function.
20:6
Thermostat function and auxiliary
function.
20:7
Solar heating via external heat
exchanger without additional
temperature sensor.
20:8
Solar heating via external heat
exchanger with additional
temperature sensor.
20:9
Solar heating of two DHW tanks.