Troubleshooting
Corrective Action
(continued)
Replacing the flow rate sensor
Note:
In the event of a fault, both sensors need to be
replaced.
1. Drain the boiler on the heating water side.
2. Pull leads from flow rate sensor
A
.
3. Undo screws and remove faulty flow rate sensor
A
.
4. Install new flow rate sensor
A
and secure with the
screws.