Vitodens 200-W B2HA 112, 150 Service
5683 710 - 09
74
Fault Codes
(continued)
Troubleshooting
*1
Control mode: Boiler/burner fully operational (fault code must be verified and reset).
Burner in fault mode: Boiler control requires manual reset before burner can resume operation.
Burner blocked: If fault cause is corrected, burner resumes operation.
*2
Detailed fault code coding address 38:xx (if available).
Fault code
on display
Detailed fault
code
*2
System behavior
*1
Cause
Corrective action
9C
-
No solar DHW heating
Tank temperature
sensor
%
cable broken
Check temperature sensor
%
on solar control module.
9E
-
Control mode
No flow rate in collector
circuit or flow rate too
low or temperature
limiter has responded
Check solar circuit
pump and solar circuit.
Acknowledge fault message.
9F
-
Control mode
Solar control module
faulty
Replace solar control module.
A3
-
Burner blocked
Flue gas temperature
sensor not properly
positioned
Properly install flue gas
temperature sensor.
A4
DO NOT
USE
-
Control mode
Max. system pressure
exceeded
Check system pressure (max.
system pressure 3 bar).
Check the function and sizing
of the diaphragm expansion
vessel. Vent the heating system
A7
-
Control mode (stays in
factory default setting)
Faulty programming
unit
Replace the programming unit.
B0
141
Burner blocked
Flue gas temperature
sensor shorted out
Check flue gas temperature
sensor (see page 81).
B1
-
Control mode (stays in
factory default setting)
Communication fault;
programming unit
(internal)
Check connections and
replace programming unit
if required.
B5
-
Control mode
(factory default setting)
Internal fault
Replace the control unit.
B7
-
Burner blocked
Boiler coding card
missing, faulty or
incorrect boiler coding
card
Plug in boiler coding card or
replace if faulty.
B8
141
Burner blocked
Flue gas temperature
sensor cable broken
Check flue gas temperature
sensor (see page 81).
BA
-
Mixing valve regulates to
a flow temperature of
68°F (20°C)
Communication fault -
accessory kit for
heating circuit 2 with
mixing valve
Check extension kit connections
and code.
BB
-
Mixing valve regulates to
a flow temperature of
68°F (20°C)
Communication error,
extension kit for heating
circuit 3 (with mixing
valve)
Check extension kit connections
and code.
BC
-
Control mode without
remote control
Communication error,
remote control Vitotrol
heating circuit 1
(without mixing valve)
Check connections, cable,
coding address “A0” in “Heating
circuit” group and remote
control unit setting.