Single Wall Venting (Room Air Dependent)
71
Vent Length Requirements
(continued)
Maximum vent pipe length - vertical
Size the exhaust vent pipe as specified
in the table on the left. This table lists
the maximum allowable vent length in
ft. and meters of the exhaust piping.
Vent diameter must not be reduced at
any point in the installation.
Table 47. Maximum allowable equivalent length - vertical
Boiler Model
System Ø
Max. equivalent
vent length (a)
H
WB1A 8-24, 8-30
2” / 51mm
3” / 76mm
4” / 102mm
*
40ft. / 12m
66ft. / 20m
79ft. / 24m
H
WB2 6-24C, 6-24
3” / 76mm
4” / 102mm
66ft. / 20m
79ft. / 24m
H
WB2 8-32
3” / 76mm
4” / 102mm
49ft. / 15m
62ft. / 19m
H
WB2 11-44
4” / 102mm
(for larger Ø system
consult Viessmann)
66ft. / 20m
H
WB2 15-60
4” / 102mm
(for larger Ø system
consult Viessmann)
49ft. / 15m
*
4” (3” to 4” increaser field supplied. Do not order Viessmann 4” parallel adaptor)
Maximum of five 90° elbows allowed in the vent system (first 90º elbow is not included).
See Fig. 47.
Minimum vent length is 3.3 ft. / 1m.
Legend
Exhaust (straight coupling) with
screen
Flashings
Support system
Combustion air intake
a Equivalent length (exhaust)
b min. 18” / 457mm
max. 48” / 1219mm
5
2
8
5
2
6
8
v
3
.8
Fig. 61
a
b