83
■
Flue gas temperature sensor
■
Flow temperature sensor
■
Cylinder temperature sensor
■
Outlet temperature sensor
■
Temperature sensor, low loss header
■
Outside temperature sensor
10
1
10
Temperature in °C
0.4
0.6
0.8
2
4
6
8
Resistance
in kΩ
30
50
70
90
110
20
Sensor type: NTC 10 k
Ω
100
10
-20 -10 0
10 20 30
Temperature in °C
6
8
20
40
60
80
200
Resistance
in kΩ
Sensor type: NTC 10 k
Ω
Fault during commissioning (fault message 416)
During commissioning, the control unit checks for cor-
rect placement of the flue gas temperature sensor. If
fault message 416 is displayed:
1.
Check whether the flue gas temperature sensor is
correctly installed (bayonet fitting). See previous
diagram.
2.
If required, correct the position of the flue gas tem-
perature sensor.
3.
Check the flue gas temperature sensor resistance.
See previous chapter. Replace faulty flue gas tem-
perature sensor if required.
4.
Turn off the ON/OFF switch.
5.
Turn the ON/OFF switch back on.
Restart the commissioning assistant.
6.
Check for leaks on the flue gas side.
Note
If fault message 416 continues to be displayed
although the flue gas temperature sensor is correctly
positioned: Initial commissioning may result in burner
faults e.g. caused by air in the gas line. Eliminate the
fault and reset the appliance.
Check temperature sensors at EM-S1 extension (ADIO electronics module) or at SDIO/SM1A electronics
module
Check temperature sensors: Installation and
service instructions of relevant accessory.
Troubleshooting
Repairs
(cont.)
6167586
Diagnosis