46
E
A
C
D
F
4x
B
Fig. 30
1.
Turn off the ON/OFF switch.
2.
Close the gas shut-off valve and safeguard against
reopening.
3.
Disconnect cables and leads from:
■
Fan motor
A
(2 plugs)
■
Ionisation electrode
B
■
Ignition unit
C
■
Earth
D
4.
Undo gas supply pipe fitting
E
.
5.
Undo 4 screws
F
and remove the burner.
Note
Cover gas connection
E
so that no small parts
can fall into it.
Commissioning, inspection, maintenance
Removing the burner
(cont.)
6167586