57
3 "Scald protection"
Setting
Explanations
The adjustable DHW temperature is limited to a maxi-
mum value.
Out
0
Scald protection OFF
Danger
Risk of injury due to increased DHW tempera-
ture.
Inform the system user of the risk from the
raised outlet temperature at the draw-off points.
In
1
Scald protection ON (maximum DHW temp. 60 °C)
Note
Even with the scald protection switched on, higher
outlet temperatures may occur at the draw-off points
in the following cases:
■
While the appliance is being calibrated
4 "Max. speed of speed-controlled primary/heating circuit pump in standard mode, heating circuit 1"
Setting
Explanations
Maximum speed of the internal circulation pump in
heating mode with standard room temperature
...
Delivered condition specified by settings specific to
the heat generator
0 to 100
Maximum speed adjustable from 0 to 100 %
5 "Screed drying"
Setting
Explanations
Not active
0
Screed drying can be set in accordance with selecta-
ble temperature/time profiles. For individual profile
curves, see chapter "Function description".
Temperature profile A
2
Temperature profile B
3
Temperature profile C
4
Temperature profile D
5
Temperature profile E
6
Temperature profile F
7
6 "Minimum heating output"
Setting
Explanations
A limit can be set on the minimum heating output for
heating mode.
...
Delivered condition specified by settings specific to
the appliance
0 to 100
Adjustable from 0 to 100 %
System configuration (parameters)
Parameter
(cont.)
6167586
Parameter