100
Temperature profile 6: Code "F1:6"
Flow temperature
°C
1
5
10
15
20
25
30
Days
50
40
30
20
10
60
Fig. 61
Ends after 21 days
Temperature profile 7: Code "F1:15"
Flow temperature
°C
1
5
10
15
20
25
30
Days
50
40
30
20
10
Fig. 62
Raising the reduced room temperature
During operation at reduced room temperature, the
reduced set room temperature can be automatically
raised subject to the outside temperature. The temper-
ature is raised in accordance with the selected heating
curve, and no higher than the set standard room tem-
perature.
The outside temperature limits for the start and end of
temperature raising can be set in coding addresses
"F8" and "F9" in the
"Heating circuit"
group.
Function description
Control functions
(cont.)
5686 293 GB
Functions