Power supply for accessories at plug
lH
(230 V ~)
Where the boiler is sited in a wet room, accessories
outside the wet area must not be connected to the
power supply at the control unit. If the boiler is not
sited in a wet room, the power supply for accessories
can be connected at the control unit. This connection
is switched directly with the ON/OFF switch of the con-
trol unit.
If the total system current exceeds 6 A, connect one or
more extensions directly to the mains supply via an
ON/OFF switch (see next chapter).
Power supply and KM BUS connection of accessories
Power supply to all accessories via heat source control unit
fÖ
fÖ
B
C
aVG
fÖ
lH
A
D
E
aVG
aVG
f-]
A
aVG
aVG
f-]
A
fÖ
aVG
aVG
f-]
A
Fig. 9
Some accessories with direct power supply
B
C
A
D
E
fÖ
fÖ
aVG
fÖ
lH
aVG
aVG
f-]
A
aVG
aVG
f-]
A
fÖ
aVG
aVG
f-]
A
Fig. 10
A
Heat source control unit
B
Extension kit for heating circuit with mixer M2
C
Extension kit for heating circuit with mixer M3
D
AM1 extension, EA1 extension and/or solar con-
trol module, type SM1
E
ON/OFF switch
fÖ
Mains input
fÖ
A Power outlet
lH
Control unit power outlet
aVG
KM BUS connection
If the current flowing to the connected working parts
(e.g. circulation pumps) is higher than the fuse rating
of the respective accessory: Only use the output con-
cerned to control an on-site relay.
Accessories
Internal fuse protec-
tion
Extension kit for heating circuit
with mixer
2 A
AM1 extension
4 A
EA1 extension
2 A
Solar control module, type
SM1
2 A
Installation sequence
Electrical connections
(cont.)
5686 293 GB
Installation