Flue gas connection and trap
1.
3.
Fig. 21
1.
Insert the boiler flue connection (accessories) into
the flue outlet as far as it will go.
2.
Connect the flue system.
Note
Connect the flue outlet to the flue with the shortest
possible run, maintaining a slight rise (min. 3°).
Avoid sharp kinks.
System size, flue outlet:
Rated heating output
Flue outlet
≤
142 kW
7
150 mm
≥
186 kW
7
200 mm
Flue system installation instructions
Note
Make all connections free of load and torque
stress.
3.
Fill the trap with water and fit it to the boiler.
Do not carry out
commissioning
until the following
conditions are met:
■
Free passage through the flue gas pipes.
■
Flue system with positive pressure is gas-tight.
■
Inspection port covers checked for secure and tight
seating.
■
Apertures for ensuring sufficient combustion air sup-
ply are open and cannot be closed off.
■
Applicable regulations on installing and commission-
ing flue systems have been followed.
Danger
Leaking or blocked flue systems or an insuffi-
cient supply of combustion air cause life threat-
ening poisoning due to carbon monoxide in the
flue gas.
Ensure the flue system functions correctly. Aper-
tures for combustion air supply must not be able
to be closed off.
Prevent condensate drainage via a wind protec-
tor.