51
Coding
Coding in the delivered condition
Possible change
56:0
Set DHW temperature adjustable
from 10 to 60 °C
56:1
Set DHW temperature adjustable
from 10 to above 60 °C
Note
Maximum value subject to coding
card
Observe the maximum permissible
DHW temperature.
58:0
Without auxiliary function for DHW
heating
58:10
to
58:60
Input of a second set DHW tempera-
ture, adjustable from 10 to 60 °C
(observe coding addresses "56" and
"63")
59:0
Cylinder heating:
Start point -2.5 K
Stop point +2.5 K
59:1
to
59:10
Start point adjustable from 1 to 10 K
below set value
5B:0
DHW cylinder directly connected to
boiler.
5B:1
DHW cylinder connected down-
stream of the low loss header.
5E:0
Circulation pump for cylinder heat-
ing remains in control mode at "Ex-
ternal blocking" signal.
5E:1
Circulation pump for cylinder heating
stops at "External blocking" signal.
5E:2
Circulation pump for cylinder heating
starts at "External blocking" signal.
5F:0
Circulation pump for cylinder heat-
ing remains in control mode at "Ex-
ternal demand" signal.
5F:1
Circulation pump for cylinder heating
stops at "External demand" signal.
5F:2
Circulation pump for cylinder heating
starts at "External demand" signal.
60:20
During DHW heating, the set boiler
water temperature is max. 20 K
higher than the set DHW tempera-
ture.
60:5
to
60:25
The differential between the set boil-
er water temperature and the set
DHW temperature is adjustable from
5 to 25 K
62:2
Circulation pump for cylinder heat-
ing with 2 min run-on time after cyl-
inder heating
62:0
Circulation pump for cylinder heating
without run-on
62:1
to
62:15
Run-on time adjustable from 1 to
15 min
63:0
Without auxiliary function for DHW
heating (only for constant tempera-
ture control units)
63:1
Auxiliary function: 1 x daily
63:2
to
63:14
Every 2 days to every 14 days
63:15
2 x daily
65:0
Without diverter valve
67:40
For solar DHW heating: Set DHW
temperature 40 °C. Above the se-
lected set temperature reheating is
suppressed.
67:0
to
67:95
Set DHW temperature adjustable
from 0 to 95 °C (limited by boiler-
specific parameters)
6F:...
Max. heating output for DHW heat-
ing in %, specified by coding card
6F:0
to
6F:100
Max. heating output for DHW heat-
ing adjustable from min. heating out-
put to 100 %
71:0
DHW circulation pump: "ON" ac-
cording to time program (only for
weather-compensated control unit)
71:1
"OFF" during DHW heating to set
value 1
Code 2
DHW/Group "3"
5839829
Codes