108
Twin boiler specification
Rated heating output
kW
240
320
400
480
560
636
Twin boiler comprises 2 boilers, each
with
kW
120
160
200
240
280
318
Total dimensions
incl. casing, boiler
flow and return; excl. boiler flue connec-
tion
Length
mm
862
862
967
967
1085
1085
Width
mm
1500
Height
mm
1650
Total weight
kg
590
590
680
680
770
770
Water capacity
l
206
206
290
290
360
360
Specification – MatriX cylinder burner
Rated boiler heating output
T
F
/T
R
50/30 °C
kW
80
120
160
200
240
280
318
Twin boiler
240
320
400
480
560
636
Burner heating output, lower/
upper output
*5
kW
15.1/
75.5
30.2/
113.2
30.2/
150.9
45.3/
188.7
45.3/
226.4
60/
264.2
60/300
Burner type
CI
75/
80 kW
CI
120/
160 kW
CI
120/
160 kW
CI
200/
240 kW
CI
200/
240 kW
CI
280/
318 kW
CI
280/
318 kW
Product ID
See boiler
Voltage
V
230
Frequency
Hz
50
Power consumption
At upper heating output
W
140.5
130
268
171
279
260
393
At lower heating output
W
19.5
28
28
29
29
26.5
26.5
Version
Modulating
Dimensions
Width a
mm
463
426
426
463
463
463
463
Length b
mm
442
481
481
655
655
731
731
Height c
mm
400
273
273
356
356
356
356
Weight
Burner with combination valve
kg
10
11
11
15
15
15
15
Gas supply pressure
G20/G25
mbar
20/25
kPa
2/2.5
Gas connection
R
1
1
½
1
½
1
½
1
½
1
½
1
½
Supply values
relative to the
max. load with
■
Natural gas E (G20) partial
load/
Full load
m
3
/h
1.6/
7.99
3.19/
11.98
3.19/
15.97
4.79/
19.97
4.79/
23.56
6.35/
27.95
6.35/
31.75
■
Natural gas LL (G25) partial
load/
Full load
m
3
/h
1.86/
9.28
3.71/
13.92
3.71/
18.57
5.57/
23.21
5.57/
27.85
7.38/
32.49
7.38/
36.9
*5
Corresponds to the rated heat input of the boiler.
Specification
Vitocrossal specification
(cont.)
5839829
Appendix