39
Coding
Coding in the delivered condition
Possible change
Set DHW temperature reheating suppression
67:40
For solar DHW heating: Set DHW
temperature 40 °C. Reheating is
suppressed above the selected set
temperature. The boiler only starts
as backup if the rise in the cylinder
temperature is too low.
67:0
to
67:95
Set DHW temperature adjustable
from 0 to 95 °C (limited by boiler-
specific parameters)
Enable DHW circulation pump
73:0
DHW circulation pump: "ON" ac-
cording to time program
(only for weather-compensated
control units)
73:1
to
73:6
"ON" from once per hour for 5 min
up to 6 times per hour for 5 min dur-
ing the time program
73:7
Constantly "ON"
Solar/Group "4"
Note
The solar group is only displayed if a solar control
module, type SM1, is connected.
Coding
Coding in the delivered condition
Possible change
Speed control solar circuit pump
02:...
Data dependent on the software
version of solar control module
SM1
02:0
Solar circuit pump is not speed-con-
trolled
02:1
With wave packet control function
Never adjust
02:2
Solar circuit pump is speed-control-
led with PWM control
Maximum cylinder temperature
08:60
The solar circuit pump is switched
off when the actual DHW tempera-
ture reaches the maximum cylinder
temperature (60 °C).
08:10
to
08:90
Set DHW temperature adjustable
from 10 to 90 °C.
Stagnation time reduction
0A:5
Temperature differential for stagna-
tion time reduction (reduction in
the speed of the solar circuit pump
to protect system components and
heat transfer medium) 5 K.
0A:0
Stagnation time reduction not active.
0A:1
to
0A:40
Temperature differential adjustable
from 1 to 40 K.
Flow rate solar circuit
0F:70
Solar circuit flow rate at the maxi-
mum pump speed 7 l/min.
0F:1
to
0F:255
Flow rate adjustable from 0.1 to
25.5 l/min,
1 step
≙
0.1 l/min.
Code 1
DHW/Group "3"
5839829
Codes