75
Type BW
2-stage
352.B027 352.B034 352.B056 352.B076
352.B097
Dimensions
Total length
mm
1848
1848
1848
2153
2153
Total width
mm
811
811
811
911
911
Handling width
mm
750
750
750
850
850
Total height
mm
1450
1450
1450
1650
1650
Total weight of standard unit
kg
555
672
723
963
1065
Sound power level
(measured with ref-
erence to EN 12102/EN ISO1914-2)
Weighted total sound power level at
B0/W35 at rated heating output
dB(A)
53
54
58
60
63
Energy efficiency class as per Commission Reg-
ulation (EU) No 813/2013
for heating, average cli-
matic conditions
Low temperature applications (W35)
A+
A++
A++
A++
A++
Medium temperature applications (W55)
A+
A+
A+
A+
A+
Heating performance data
as per Commission
Regulation (EU) No 813/2013 (average climatic con-
ditions)
Low temperature applications (W35)
■
Energy efficiency
η
S
%
147
150
153
154
154
■
Seasonal coefficient of performance
(SCOP)
3.87
3.96
4.03
4.04
4.06
Medium temperature applications (W55)
■
Energy efficiency
η
S
%
112
115
117
118
118
■
Seasonal coefficient of performance
(SCOP)
3.01
3.08
3.12
3.14
3.15
Type BW
2-stage
3-stage
352.B114 352.B132 352.B156 353.B172
353.B198
Electrical values, heat pump
Rated voltage
3/N/PE 400 V/50 Hz
Starting system
Soft start
Starting current per compressor
A
126
144
188
126
144
Total starting current (per stage)
A
208
237
245
262
300
Max. total operating current
A
137
156
187
191
220
Max. total power consumption
kW
78
89
97
110
125
Cos
φ
compressor at max. output
B15/W35
0.70
0.66
0.57
0.70
0.66
Internal protection per compressor
(3/N/PE)
gG63A
gG80A
gG100A
gG63A
gG80A
Internal protection for pumps and valves
(3/N/PE)
C40A
C40A
C40A
C40A
C40A
Max. permissible power cable protection
on site
A
160
160
200
200
250
IP rating
IP 20
IP 20
IP 20
IP 20
IP 20
Specification
Specification – Vitocal 350-G Pro
(cont.)
5855865
Appendix
Summary of Contents for BW 352.B027
Page 83: ...83 5855865...