13
Installation room requirements
!
Please note
Unfavourable ambient conditions can lead to
malfunctions and appliance damage.
■
The installation room must be dry and free
from the risk of frost.
■
Ensure ambient temperatures between
3 and 30 °C.
Danger
Dust, gases and vapours can be damaging to
health and trigger explosions.
Avoid dust, gases and vapours in the installation
room.
!
Please note
Overloading the floor can result in damage to
the building structure.
Observe the permissible floor load. Take the
weight of the appliance into account.
Weight
Type
Weight in kg
BW 352.B027
555
BW 352.B034
672
BW 352.B056
723
BW 352.B076
963
BW 352.B097
1065
BW 352.B114
1113
BW 352.B132
1209
BW 352.B156
1260
BW 353.B172
1604
BW 353.B198
1678
■
To prevent the transmission of structure-borne noise,
never site the appliance above ceilings with wooden
joists (e.g. in the attic).
■
Level the appliance horizontally.
Where floors are uneven, distribute the load evenly
across the feet.
■
Observe minimum room volume (to EN 378).
Observe additional country-specific regulations.
■
Observe the floor area and minimum clearances
(see following chapter).
Minimum room volume, based on the available air
volume
Taking into account the type and charge weight of the
refrigerant used, the following minimum room volumes
result.
Note
Refrigerant charge, see "Specification" or type plate.
Type
Minimum room volume
in m
3
BW 352.B027
17
BW 352.B034
21
BW 352.B056
26
BW 352.B076
30
BW 352.B097
40
BW 352.B114
48
BW 352.B132
56
BW 352.B156
68
BW 353.B172
76
BW 353.B198
88
Preparing for installation
Transport and siting requirements: Heat pump
(cont.)
5855865
Installation