Vitocal 350, type BWH 110 and WWH 110
A
Heating output
B
Refrigerating capacity
C
Power consumption
D
T
HV
= 35 °C
E
T
HV
= 45 °C
F
T
HV
= 55 °C
G
T
HV
= 65 °C
Note
COP details in the following tables and diagrams calculated with
reference to DIN EN 255.
Performance data type BWH 110
Operating point
B0/W35
B2/W55
B2/W65
Heating output
kW
11.00
13.20
13.20
Refrigerating capa-
city
kW
8.45
9.00
8.10
Power consumption
kW
2.55
4.20
5.10
Coefficient of Performance
∊
(COP)
4.31
3.14
2.59
Performance data type WWH 110
Operating point
W10/W35
W8/W55
W8/W65
Heating output
kW
14.10
14.60
14.90
Refrigerating capa-
city
kW
11.40
10.30
9.45
Power consumption
kW
2.70
4.30
5.15
Coefficient of Performance
∊
(COP)
5.22
3.39
2.83
5822
1
19-7
G
B
22
VIESMANN
VITOCAL 300/350
Output diagrams for the Vitocal 350