Vitocal 300, type BW 226 and WW 226 (two-stage)
A
Heating output
B
Refrigerating capacity
C
Power consumption
D
T
HV
= 35 °C
E
T
HV
= 45 °C
F
T
HV
= 55 °C
Performance data type BW 226
Operating point
B0/W35
B2/W45
B2/W55
Heating output
kW
28.00
28.80
27.80
Refrigerating capa-
city
kW
21.90
21.30
18.70
Power consumption
kW
6.10
7.50
9.10
Coefficient of Performance
∊
(COP)
4.57
3.82
3.00
Performance data type WW 226
Operating point
W10/W35
W8/W45
W8/W55
Heating output
kW
36.60
33.40
32.20
Refrigerating capa-
city
kW
30.40
25.70
22.80
Power consumption
kW
6.20
7.70
9.40
Coefficient of Performance
∊
(COP)
5.87
4.31
3.40
5822
1
19-7
G
B
20
VIESMANN
VITOCAL 300/350
Output diagrams for the Vitocal 300 (two-stage)
(cont.)