Vitocal 300, type BW 116 and WW 116 (single stage)
A
Heating output
B
Refrigerating capacity
C
Power consumption
D
T
HV
= 35 °C
E
T
HV
= 45 °C
F
T
HV
= 55 °C
Performance data type BW 116
Operating point
B0/W35
B2/W45
B2/W55
Heating output
kW
16.30
16.70
16.10
Refrigerating capa-
city
kW
12.70
12.20
10.70
Power consumption
kW
3.60
4.50
5.40
Coefficient of Performance
∊
(COP)
4.53
3.71
2.98
Performance data type WW 116
Operating point
W10/W35
W8/W45
W8/W55
Heating output
kW
21.50
19.60
18.90
Refrigerating capa-
city
kW
17.80
15.00
13.30
Power consumption
kW
3.70
4.60
5.60
Coefficient of Performance
∊
(COP)
5.81
4.26
3.37
5822
1
19-7
G
B
16
VIESMANN
VITOCAL 300/350
Output diagrams for the Vitocal 300 (single stage)
(cont.)