Vitocal 300, type BW 108 and WW 108 (single stage)
A
Heating output
B
Refrigerating capacity
C
Power consumption
D
T
HV
= 35 °C
E
T
HV
= 45 °C
F
T
HV
= 55 °C
Performance data type BW 108
Operating point
B0/W35
B2/W45
B2/W55
Heating output
kW
8.30
8.50
8.10
Refrigerating capa-
city
kW
6.50
6.25
5.30
Power consumption
kW
1.80
2.25
2.75
Coefficient of Performance
∊
(COP)
4.61
3.77
2.95
Performance data type WW 108
Operating point
W10/W35
W8/W45
W8/W55
Heating output
kW
10.90
9.90
9.50
Refrigerating capa-
city
kW
9.00
7.55
6.65
Power consumption
kW
1.90
2.35
2.85
Coefficient of Performance
∊
(COP)
5.74
4.21
3.33
5822
1
19-7
G
B
VITOCAL 300/350
VIESMANN
13
Output diagrams for the Vitocal 300 (single stage)