59
Coding in the delivered condition
Possible change
Service interval in months
23:0
No time set for burner service in-
terval
23:1
to
23:24
Time interval adjustable from 1 to
24 months
Service status
24:0
"Service"
not shown on the dis-
play
24:1
"Service"
is shown on the display
(address is automatically set and
must be manually reset after a serv-
ice has been carried out)
"DHW"
Select
"DHW"
(see page 57).
Coding
Coding in the delivered condition
Possible change
Set DHW temperature reheating suppression
67:40
For solar DHW heating: Set DHW
temperature 40 °C. Reheating is
suppressed above the selected set
temperature.
67:0
to
67:95
Set DHW temperature adjustable
from 0 to 95 °C (limited by boiler-
specific parameters)
Enable DHW circulation pump
73:0
DHW circulation pump: "ON" ac-
cording to time program
73:1
to
73:6
"ON" from once per hour for 5 min
up to 6 times per hour for 5 min dur-
ing the time program
73:7
Constantly "ON"
"Solar"
Select
"Solar"
(see page 57).
Note
The solar group is only displayed if a solar control
module, type SM1, is connected.
Coding
Coding in the delivered condition
Possible change
Speed control solar circuit pump
02:...
Data dependent on the software
version of solar control module
SM1
02:0
Solar circuit pump is not speed-con-
trolled
02:1
With wave packet control function
Never adjust
02:2
Solar circuit pump is speed-control-
led with PWM control
Maximum cylinder temperature
08:60
The solar circuit pump is switched
off when the actual DHW tempera-
ture reaches the maximum cylinder
temperature (60 °C).
08:10
to
08:90
Set DHW temperature adjustable
from 10 to 90 °C.
Codes
Code 1
(cont.)
6136330
Codes