34
Table no. 6 Boiler output adjustment - VIADRUS HERCULES ECO 10
Boiler output
[kW]
Time for fuel
feeding [s]
Time for fuel
afterburning [s]
Quantity of combustion air [%]/
Adjustment of starling flap of the fan on nr.
12,1
25
90
5 / 0,5
12,6
27
90
5 / 0,5
13
30
90
10 / 1
14
33
90
10 / 1
15
35
90
15 / 1,5
16
35
84
15 / 1,5
17
35
78
20 / 2
18
35
72
20 / 2
19
35
66
25 / 2,5
20
35
60
25 / 2,5
21
35
56
30 / 3
22
35
53
30 / 3
23
35
50
35 / 3,5
24
35
46
35 / 3,5
25
35
43
40 / 4
26
35
40
40 / 4
27
35
37
45 / 4,5
28
35
35
50 / 5
29
35
32
55 / 5,5
30
35
30
60 / 6
31
35
28
65 / 6,5
32
35
26
70 / 7
33
35
24
70 / 7
34
35
22
75 / 7,5
35
35
20
80 / 8
36
35
18
80 / 8
37
35
16
85 / 8,5
38
35
15
90 / 9
39
35
14
90 / 9
40
35
13
95 / 9,5
41
35
11
100 / 10
42
35
10
100 / 10
0
10
20
30
40
50
60
70
80
90
100
10
15
20
25
30
35
40
45
Fig. no. 24
Boiler output graph on time of fuel afterburning at the same time for fule feeding
(10 s) for boiler VIADRUS HERCULES ECO 10