Installation manual Generator Sets GHX / GLX
IMPORTANT
The size of ventilation openings must be sufficient for both the generator set and the
main propulsion engine(s) located in the same compartment.
The combustion air requirement for the generator set is as shown in the table below:
Generator set model
Combustion air flow
Ventilation opening
GHX 8
1.1 m
3
/min
( 37 cu.ft/min )
58 cm
2
( 9 sq.in. )
GHX 9
1.3 m
3
/min
( 44 cu.ft/min )
70 cm
2
( 11 sq.in. )
GHX 14
1.9 m
3
/min
( 67 cu.ft/min )
105 cm
2
( 16 sq.in. )
GHX 17
2.2 m
3
/min
( 78 cu.ft/min )
123 cm
2
( 19 sq.in. )
GHX 24
3.2 m
3
/min
( 111 cu.ft/min )
175 cm
2
( 27 sq.in. )
GLX 6
0.8 m
3
/min
( 30 cu.ft/min )
47 cm
2
( 7 sq.in. )
GLX 7
1.1 m
3
/min
( 37 cu.ft/min )
58 cm
2
( 9 sq.in. )
GLX 14
1.9 m
3
/min
( 67 cu.ft/min )
105 cm
2
( 16 sq.in. )
GLX 17
2.2 m
3
/min
( 78 cu.ft/min )
123 cm
2
( 19 sq.in. )
GLX 20
2.6 m
3
/min
( 93 cu.ft/min )
146 cm
2
( 23 sq.in. )
GLX 24
3.2 m
3
/min
( 111 cu.ft/min )
175 cm
2
( 27 sq.in. )