DGT / DGT60 / DGTQ / DGTP
51
7. ANALOGUE OUTPUT (DGT4 AN, DGTQ AN and DGTP AN version)
In all the functioning modes, through an optional interface, it is possible to use an analogue output configurable at 0 –
10V, 0 – 20 mA or 4 – 20 mA. The voltage and the output current from the interface are proportional to the gross
weight or net weight present on the scale. In regards to the electrical connection scheme, refer to the section 11
"ELECTRICAL SCHEMES".
Note:
The analogue output is updated every 50ms and takes on the value corresponding to the weight converted in
that instant; therefore if the filter is slowed on the weight, the analogue output also slows down.
For configuring the parameters, one should enter the setup environment and enter in the
SEtuP
>>
ConFiG
>>
Anout
step.
An.out
ModE
Ao no
Ao n
Ao G
AoMA
AoZE
xxxxxx
xxxxxx
AoMi
xxxxxx
SiGn (§)
PoSit, nEGAt
SEtuP
Chan (§)
1..4
ChAn
By entering this step, one selects the channel to be configured (from 1 to 4).
NOTE:
The parameter is not displayed if one has set "
dEP.CH
" in the
tYPE
parameter or in case of one channel
application, step
SEtuP
>>
ConFiG
>>
nChAn.
ModE
By entering this step one selects the tyep of analogue output:
Ao no
= analogue output disabled.
Ao G
= analogue output on gross weight.
Ao n
= analogue output on net weight.
Once the functioning mode is confirmed, one sets the values of the analogue output; in other words, the
digital/analogue converter values are entered (between 0 and 65535) to which corresponds a certain output value in
voltage or in current.
In this configuration the instrument keys take on the following meanings (functions):
ZERO
It decreases the selected digit (blinking).
TARE
It increases the selected digit (blinking)
MODE
It selects the digit (blinking) from left to right.
By pressing once after have a value has been entered, it enables the corresponding output
analogue value, (allowing the check) but remains still inside the step in case of a new
modification. By pressing a second time (on the same entered value), it confirms and exits
the step.
C
It allows to quickly zero the present value.
NOTE:
The functioning mode is just one for all the configured channels.
AoMAX
By entering this step, one sets the maximum value of the analogue output, in other words:
−
with functioning on the positive weight
the value corresponding tohe full scale capacity and in the overload
condition.
−
with functioning on the negative weight
the value corresponding to the under load condition.
This value can be anywhere between 0 and 65535 (values of the digital/analogue converter); if a higher digit is
Summary of Contents for DGT
Page 65: ...DGT DGT60 DGTQ DGTP 65 11 CONNECTION SCHEMES 11 1 DGT4 DGT60 DGT4 AN MOTHERBOARD I O BOOT J 1...
Page 68: ...DGT DGT60 DGTQ DGTP 68 11 2 DGT4 PB MOTHERBOARD I O BOOT J 1...
Page 71: ...DGT DGT60 DGTQ DGTP 71 11 3 DGTQ DGTQ AN BOARDS...
Page 72: ...DGT DGT60 DGTQ DGTP 72 I O BOOT J1 J2 CAL...
Page 76: ...DGT DGT60 DGTQ DGTP 76 11 4 DGTQ PB BOARDS...
Page 77: ...DGT DGT60 DGTQ DGTP 77...
Page 81: ...DGT DGT60 DGTQ DGTP 81 11 5 DGTP DGTP AN DGTP PB MOTHERBOARD...