7. Mounting
Always disconnect the power supply before opening the unit.
Heat load to be dissipated from enclosure should not exceed specific cooling output of the unit at any
condition. At cooling unit selection always cater for a safety margin of at least 15% extra cooling
output in the worst conditions. Air inlets and outlets must be completely free from obstruction.
Ensure that flows of air leaving and entering the cooling unit, internal and external, are not obstructed.
Cooling unit enclosure air suction hole must be installed in the highest possible point. When installing
the unit on a door ensure it can take the weight.
Before drilling the enclosure ensure the fixing elements and couplings will not interfere with the
equipment inside the enclosure itself. Disconnect power before starting any work inside the enclosure.
Following this 1:1 Scale Drilling Template drill the holes and make the required cuts on the enclosure.
This template may have been affected by storage conditions, please check this template by verifying
values of the largest dimensions before drilling. Fit the sealing strip on the cooling unit on the side
connected to the enclosure and follow the installation diagram.