12. Trouble shooting
Failure
Condition
Cause
Solution
Unit
doesn't
cool
Internal fan does not work
Power not connected.
Verify power supply
Internal fan works, external fan
and compressor don't work
Enclosure temperature is
below
setting temperature (St)
Verify values of parameter
"St"
Door switch contact is open
Verify door switch
Controller doesn't work
Replace controller
Internal fan works, external fan
and compressor don't work.
Display shows alternating OFF
and temperature
The sequence of the phases
inside the power supply
connector is incorrect
Change phases inside
power
supply connector
Unit
doesn't
cool
External and internal fan work,
compressor does not work
Compressor motor electrical
failure
Have compressor replaced
by qualified service
technician
Capacitor for compressor failed Replace capacitor
Compressor works, external fan
doesn't work
External fan needs to be
replaced
Replace external fan
Enclosure
temperature
too hot
Compressor and fans (external
and internal) work all the time
Cooling unit undersized
Enclosure needs a cooling
unit with with higher
capacity
Compressor and external fan
work in alternating mode
(ON / OFF)
Thermal compressor protector
triggered
Verify if ambient
temperature
is too high,clean condenser
Refrigerant leakage
Contact dealer/service center
Excessive
condensate
Enclosure door open
Ambient air gets into the
enclosure
Ensure door is closed, add
a door switch and connect
it to controller
Enclosure door closed
Enclosure IP protection class
is below IP54
Seal all openings of the
enclosure
Damaged or misplaced sealing
strip
Repair sealing strip
accordingly
13. Maintenance & Cleaning
Always switch power supply off before starting any maintenance on
the unit.
The cooling unit is generally maintenance free and can be operated without filters in most
environments. For units with filters these should be checked, cleaned and if necessary replaced on a
regular basis. In addition the unit should have regular functional tests (approx. every 2,000 hours
depending on the grade of ambient pollution).
Disposal.
The cooling unit contains R134a refrigerant and small quantities of lubricating oil. Replacement,
repairs and final disposal must be done according to the regulations of each country for these
substances.
14. Transport & Storage
Malfunction due to transport damage
On delivery the carton box containing the unit must be examined for signs of transport damage. Any
transport damage to the carton box could indicate that the unit itself has been damaged in transit
which in the worst case could mean that the unit will not function.