Version Nr. 1-1 - 23.08.2017

Doc. Nr. 994020009

12 / 14

12. Trouble shooting

Failure

Condition

Cause

Solution

 Unit
 doesn't
 cool

 Internal fan does not work

 Power not connected.

 Verify power supply

 Internal fan works, external fan
 and compressor don't work

 Enclosure temperature is
below
 setting temperature (St)

 Verify values of parameter
 "St"

Door switch contact is open

 Verify door switch

Controller doesn't work

 Replace controller

 Internal fan works, external fan
 and  compressor don't work.
 Display shows alternating OFF 
 and temperature

 The sequence of the phases
 inside the power supply
 connector is incorrect

 Change phases inside
power 
 supply connector

 Unit
 doesn't
 cool

 External and internal fan work,
 compressor does not work

 Compressor motor electrical
 failure

 Have compressor replaced  
 by qualified service
technician

 Capacitor for compressor failed  Replace capacitor

 Compressor works, external fan
 doesn't work

 External fan needs to be
 replaced

 Replace external fan

 Enclosure
 temperature 
 too hot

 Compressor and fans (external
 and internal) work all the time

 Cooling unit undersized

 Enclosure needs a cooling
 unit with with higher
capacity

 Compressor and external fan 
 work in alternating mode
(ON / OFF)

 Thermal compressor protector
 triggered 

 Verify if ambient
temperature
 is too high,clean condenser

 Refrigerant leakage

Contact dealer/service center

 Excessive 
 condensate

 Enclosure door open

 Ambient air gets into the  
 enclosure

 Ensure door is closed, add
 a door  switch and connect
 it to controller

 Enclosure door closed

 Enclosure IP protection class 
 is  below IP54

 Seal all openings of the
 enclosure

 Damaged or misplaced sealing
 strip

 Repair sealing strip
 accordingly

13. Maintenance & Cleaning

Always switch power supply off before starting any maintenance on
the unit.

The cooling unit is generally maintenance free and can be operated without filters in most
environments. For units with filters these should be checked, cleaned and if necessary replaced on a
regular basis. In addition the unit should have regular functional tests (approx. every 2,000 hours
depending on the grade of ambient pollution).
Disposal.
The cooling unit contains R134a refrigerant and small quantities of lubricating oil. Replacement,
repairs and final disposal must be done according to the regulations of each country for these
substances.

14. Transport & Storage

Malfunction due to transport damage
On delivery the carton box containing the unit must be examined for signs of transport damage. Any
transport damage to the carton box could indicate that the unit itself has been damaged in transit
which in the worst case could mean that the unit will not function.

Summary of Contents for OC 4020009

Page 1: ...regulations 2 3 Safety instructions 3 4 Technical information 4 5 Technical data 4 7 Mounting 5 8 Electrical connection 6 9 Controller Layout Description 8 10 Wiring diagram 9 11 Taking into operatio...

Page 2: ...instruction manual must be adhered to General danger Indicates compulsory safety regulations which are not covered by a specific pictogram such as one of the following High electric voltage Indicates...

Page 3: ...ds to Safety instructions Instructions on taking the cabinet out of operation Instructions on the prevention of unauthorised cabinet reconnection The electric equipment meets the valid safety regulati...

Page 4: ...e ambient air The unit can function without problems in extreme ambient conditions e g dusty and oily air with a standard operating temperature ranging between 20 C and 55 C Units can be ordered with...

Page 5: ...ooling unit enclosure air suction hole must be installed in the highest possible point When installing the unit on a door ensure it can take the weight Before drilling the enclosure ensure the fixing...

Page 6: ...equire an external power source if wired to operate external components indicator lamps switches The load on these contacts is not to exceed 30V DC 4 A or 120 250V AC 4 A If wired to external componen...

Page 7: ...on or off via a door contact switch terminal 3 4 When delivered the door contact terminals are bridged To connect the door contact switch Remove the bridge from terminals 3 4 Connect the door contact...

Page 8: ...tional HC Heater control AC Alarm control TC Temperature control OS Optional Sensor DC Door contact AO Alarm output PI Power in CO Compressor out CC Capacitor compressor AFO Umgebungsl fter aus CAF Ko...

Page 9: ...tral line fuse FL Live line fuse Temp Control temperature adjustment potentiometer Alarm Alarm temperature adjustment potentiometer Heater Heater temperature adjustment potentiometer 1 2 Alarm contact...

Page 10: ...Version Nr 1 1 23 08 2017 Doc Nr 994020009 10 14...

Page 11: ...erefore be allowed to stand for at least 30 min before being connected to the mains and taken into operation Upon connection the internal fan will start working If the temperature inside the enclosure...

Page 12: ...protector triggered Verify if ambient temperature is too high clean condenser Refrigerant leakage Contact dealer service center Excessive condensate Enclosure door open Ambient air gets into the encl...

Page 13: ...ould be returned in the original packing or in a packing case and must be strapped to a pallet If the unit cannot be returned in the original packing please ensure that A space of at least 30 mm must...

Page 14: ...94020009 14 14 15 Parts supplied 1 x Outdoor cabinet air conditioner 1 x Instruction manual 1 x CE Conformity declaration 1 x Connector with bridged door contacts 1 x Lid deflector with fasteners 1m P...

Reviews: