8. Electrical connection

High electric voltage present. Installation, maintenance, cleaning and
any other work must be carried out by qualified personnel only. The
personnel must ensure that for the duration of this work the unit and
the cabinet are disconnected from the electrical supply and protected
against unauthorised/accidental reconnection. 

Note: As soon as preperations are finished, mounting procedures may proceed.

Connection to the main electrical supply
The mains connection is made via a connector / terminal block. To connect the unit to the mains
proceed as follows:

Take the control cabinet out of operation in the prescribed manner.

See the connection details on the circuit diagram.

Attention

Between contact 3 & 4 there is a 12V DC potential. These connections are to be connected to a door
switch only! If no door switch is used, these contacts are to be bridged and protected from
unauthorized and/or accidental external contact. Contacts 1 & 2 are potential free and require an
external power source if wired to operate external components (indicator lamps, switches...). The load
on these contacts is not to exceed 30V DC, 4 A or 120/250V AC, 4 A. If wired to external components it
must be ensured that the wiring and connections are double insulated and safe against touch and
protected from unauthorized and/or accidental external contact.

Ensure that the correct polarity is maintained. The fans should have
clockwise rotation.

Fault warning connection

The fault warning is connected via terminals 1 & 2 on the connection terminal block. The temp.
adjustment range is between 25°C (left-hand stop) and 55°C (right-hand stop). The alarm temp. is
preset at 55°C.

To change the alarm setting:

Remove the outer cover.

Remove the fixing screws from the PCB cover and the earth wire from inside it.

Lift off the PCB cover

Using a screwdriver turn the alarm temp. potentiometer on the PC-board slightly to the right (higher)

or the left (lower)
please note that the setting for the alarm signal must be at least 5°C higher than the setting for the

cabinet's internal temperature
Close the unit as prescribed.

Check that the new setting meets requirments and if not repeat the above process.

Door contact switch connection

Summary of Contents for OC 4020009

Page 1: ...regulations 2 3 Safety instructions 3 4 Technical information 4 5 Technical data 4 7 Mounting 5 8 Electrical connection 6 9 Controller Layout Description 8 10 Wiring diagram 9 11 Taking into operatio...

Page 2: ...instruction manual must be adhered to General danger Indicates compulsory safety regulations which are not covered by a specific pictogram such as one of the following High electric voltage Indicates...

Page 3: ...ds to Safety instructions Instructions on taking the cabinet out of operation Instructions on the prevention of unauthorised cabinet reconnection The electric equipment meets the valid safety regulati...

Page 4: ...e ambient air The unit can function without problems in extreme ambient conditions e g dusty and oily air with a standard operating temperature ranging between 20 C and 55 C Units can be ordered with...

Page 5: ...ooling unit enclosure air suction hole must be installed in the highest possible point When installing the unit on a door ensure it can take the weight Before drilling the enclosure ensure the fixing...

Page 6: ...equire an external power source if wired to operate external components indicator lamps switches The load on these contacts is not to exceed 30V DC 4 A or 120 250V AC 4 A If wired to external componen...

Page 7: ...on or off via a door contact switch terminal 3 4 When delivered the door contact terminals are bridged To connect the door contact switch Remove the bridge from terminals 3 4 Connect the door contact...

Page 8: ...tional HC Heater control AC Alarm control TC Temperature control OS Optional Sensor DC Door contact AO Alarm output PI Power in CO Compressor out CC Capacitor compressor AFO Umgebungsl fter aus CAF Ko...

Page 9: ...tral line fuse FL Live line fuse Temp Control temperature adjustment potentiometer Alarm Alarm temperature adjustment potentiometer Heater Heater temperature adjustment potentiometer 1 2 Alarm contact...

Page 10: ...Version Nr 1 1 23 08 2017 Doc Nr 994020009 10 14...

Page 11: ...erefore be allowed to stand for at least 30 min before being connected to the mains and taken into operation Upon connection the internal fan will start working If the temperature inside the enclosure...

Page 12: ...protector triggered Verify if ambient temperature is too high clean condenser Refrigerant leakage Contact dealer service center Excessive condensate Enclosure door open Ambient air gets into the encl...

Page 13: ...ould be returned in the original packing or in a packing case and must be strapped to a pallet If the unit cannot be returned in the original packing please ensure that A space of at least 30 mm must...

Page 14: ...94020009 14 14 15 Parts supplied 1 x Outdoor cabinet air conditioner 1 x Instruction manual 1 x CE Conformity declaration 1 x Connector with bridged door contacts 1 x Lid deflector with fasteners 1m P...

Reviews: