88 Appendix 2 Alarm List
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
SN
Alarm
device
Alarm name
Alarm category
Related
relay
Alarm description
21
M831D
system
Grid is on
Observation
22
Hi Ambient Temp
Observation
23
Lo Ambient Temp
Observation
24
Sensor Fault
Observation
25
DI1 Alarm
Critical
26
DI2 Alarm
Critical
27
DI3 Alarm
Critical
28
DI4 Alarm
Critical
29
DI5 Alarm
Critical
30
DI6 Alarm
Critical
31
DI7 Alarm
Critical
32
DI8 Alarm
Critical
33
IB Comm Fail
Critical
34
Rect Group
Multi-Rect Fail
Critical
Relay 4
This alarm happens when rectifier AC
power fails.
35
Rectifier Lost
Major
Relay 4
The controller can memorize the number
of rectifiers. If the number of detected
rectifiers is less than the number
memorized by the controller, then this
alarm occurs. This alarm can only be
ceased manually
36
ECO Active
Observation
37
AllRectCommFail
Major
38
ECO Cycle Alarm
Observation
39
Rectifier
AC Failure
Major
Relay 4
This alarm happens when rectifier AC
power fails
40
Rect Temp High
Observation
None
This alarm happens when rectifier has
over temperature fault
41
Rect Fault
Major
Relay 4
This alarm happens when rectifier fails
42
Over Voltage
Major
Relay 4
This alarm happens when DC output
over voltage occurs
43
Rect Protected
Observation
None
This alarm happens when rectifier is
under protection
44
Fan Failure
Major
Relay 4
This alarm happens when rectifier fan
fails.
45
Current limit
Observation
None
This alarm happens when rectifier limits
its output current
46
Rect Comm Fail
Major
Relay 4
This alarm happens when rectifier
communication fails
47
Derated
Observation
The alarm happens when rectifier power
limit occurs
48
Curr Shara Alm
Observation
The alarm happens when rectifier current
unbalance occurs
49
Low AC Protect
Major
50
Battery
Group
ShortBatTestRun
Observation
The alarm happens during short test
51
EQ for Test
Observation
The alarm happens during pre-boost
charging
52
Manual Test
Observation
The alarm happens during manual
battery test
53
Planned Test
Observation
The alarm happens during planed battery
test
54
AC Fail Test
Observation
The alarm happens during AC power
failure test