Chapter 3 Installation 49
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
JP2
JP1
1J1
1J3
1J2
J0
J1
J2
J3
J4
J5
J6
J8
J9
J10
J7
+12
Signal output
PGND
1
2
3
+12
PGND
1
2
3
+12
PGND
1
2
3
J11 J12 J13
1
8
+12
PGND
P101-3 socket
A6V6FU11 board
Signal output
Signal output
Signal output
Figure 3-35 Connection of temperature sensor
3. AD592BN is current type temperature sensor. Ensure that the sixth position (temperature sensor selection position)
of the DIP switch on the DC distribution cabinet has
been set “OFF”. For the setup method, refer to 4.3.1 Setting
4. The temperature probe should be put in the battery room where it can best incarnate the battery temperature.
When fixing it, do not connect it to any other exothermic equipment or metal conductor.