52 Chapter 4 Testing
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
1
2
3
4
5
6
7
8
OFF
ON
Figure 4-1 DIP switch
Table 4-1 Setting list of DIP switch for AC distribution cabinet address
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Corresponding address in the controller
0
0
0
0
0
64
1
0
0
0
0
65
0
1
0
0
0
66
1
1
0
0
0
67
0
0
1
0
0
68
1
0
1
0
0
69
0
1
1
0
0
70
1
1
1
0
0
71
Note
Address of the AC distribution cabinet default setting from factory is 64, if there are multiple AC screens, set the cabinets address
to 64, 65,…,71.
The setting explanation of bits 6 to 8 is given in Table 4-2.
Table 4-2 Setting list of DIP switch
Bit
Definition
Default
Setting explanation
6
Temperature sensor type
ON
ON: voltage type temperature sensor; OFF: current type temperature sensor;
AC distribution cabinet can ignore this item
7
Buad rate
OFF
ON: 9600bps; OFF: 19200bps; AC distribution cabinet if OFF by default
8
Reserved
ON
ON
Setting DIP switches of PD380/630AFA AC distribution cabinet
The setting dip switch of AC distribution cabinet is shown in Figure 4-2.
1
2
3
4
5
6
7
8
RS485 address
ON
Reserved
Reserved
1
2
3
4
5
6
7
8
Figure 4-2 DIP switch
Position
‘ON’ represents ‘1’, and ‘OFF’ represents ‘0’. See Table 4-3 for details.
Table 4-3
Setting DIP switches of DC distribution cabinet
Bit
Definition
Setting explanation
1 ~ 4
Communication
address
Bits 1 is low, Bits 4 is high
AC distribution cabinet address: 00000~11100 (controller address: 64 ~ 71):
1
2
3
4
1
2
3
4
5
Reserved
Set it to
‘OFF’ during test
6
Reserved
Set it to
‘OFF’ during test
7
Reserved
Set it to
‘OFF’ during test
8
Reserved
Set it to
‘OFF’ during test