48 Chapter 3 Installation
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
RS485 communication cable
AC cabinet 1
Rectifier cabinet
1
DC cabinet
1
AC cabinet 48V power cable
0V
-48V
0V
-48V
0V
-48V
A2V4FA1
A6V6FU11
Monitor
RS485 communication cable
AC cabinet 48V power cable
RS485 communication cable
AC cabinet 2
Rectifier cabinet
2
Rectifier cabinet
3
DC cabinet
2
DC cabinet
3
Sampling transfer
board of AC
Monitoring
board
A2V6FX1
A2V4FA1
Sampling transfer
board of AC
Signal transfer
board
A6V6FU11
A2V6FX1
Monitoring
board
Signal transfer
board
A6V6FU11
A2V6FX1
Monitoring
board
Signal transfer
board
A6V6FU11
A2V6FX1
Monitoring
board
Signal transfer
board
A6V6FU11
A2V6FX1
Monitoring
board
Signal transfer
board
Configuring PD380/400AFH & PD380/400AFH AC distribution cabinet
HDU1U11
Monitoring
board
A1V8FA1
电流采样板
HDU1U11
Monitoring
board
A1V8FA1
电流采样板
AC cabinet 1
AC cabinet 2
Rectifier
cabinet 1
Rectifier
cabinet 2
Rectifier
cabinet 3
DC cabinet 1
DC cabinet 2
DC cabinet 3
Monitor
0V
-48V
0V
-48V
0V
-48V
A6V6FU11
Monitoring
board
A2V6FX1
Signal transfer
board
RS485communication cable
RS485communication cable
AC cabinet 48V power cable
AC cabinet 48V power cable
RS485communication cable
A6V6FU11
Monitoring
board
A6V6FU11
Monitoring
board
A2V6FX1
Signal transfer
board
A2V6FX1
Signal transfer
board
Current sampling
board
Current sampling
board
Configuring PD380/630AFA AC distribution cabinet
Figure 3-34 Connection diagram of power system communication cable and 48V DC auxiliary power source cable(front view)
3.6 Installing Options
Installing temperature sensor
AD592BN temperature sensor is an option. And the wiring steps are shown as follows:
1. Make cable connection to the temperature sensor. Pay attention to the cable definition and color.
2. Connect P101-3 socket which is connected to 3-core cable of the temperature sensor to J4, J5 and J6 sockets on
the monitoring board of DC distribution cabinet (model: A6V6FU11), as shown in Figure 3-35. J4 has temperature
compensation function. J5 and J6 perform temperature display function but not temperature compensation function.