Vertiv
|
NetSure™ 2100 Series -48 VDC Power System Installation Manual (IM582138000)
|
Rev. C
66
Load Distribution Wiring, Input Battery Wiring, and CO Ground Wiring (Lists BA) (cont’d from
previous page)
-48 VDC Load Terminal Blocks:
Wire Size Capacity:
22 AWG to 10 AWG.
Recommended Torque:
5.3 in-lbs.
-4
8V
Load Leads
-4
8V
Load Leads
Loa
d R
et
ur
n Le
ads
Circuit B
reaker
s #1 thr
ough #7
List BA Distribution
Unit (Top View)
Load Distribution
Circuit Breakers
Load Distribution
Fuses
Front
Front
Front Circui
t Breaker
Cover
Partially slide distribution
unit out of shelf for wiring.
Observe proper polarity
when making battery
and load connections.
WARNING!
-48 VDC Load Terminal Blocks:
Wire Size Capacity:
22 AWG to 12 AWG.
Recommended Torque:
4.4 in-lbs.
-4
8V
Load Leads
Loa
d R
et
ur
n Le
ads
Fuses
#1 t
hrough
#6
Distribution Wire
Routing Channel
Secure distribution wiring to
rear of sheetmetal distribution
unit slide (tie points shown
below). Leave slack in wires at
rear to allow distribution unit to
slide in and out after wiring.