APPENDICES
Appendix A: Specifications
0U
1U
2U
Input Power Configurations; vary by model and region
Single-Phase Input; CE-Mark
240 VAC, 16 A; also UL-listed
3.8 kW
230 V, 32 A
7.3 kW
Three-phase Input; CE-Mark
230/400 V, 16 A
11 kW
230/400 V, 32 A
22 kW
Single-Phase Input, UL-Listed
120 VAC, 12A
1.4 kW
120 VAC, 16 A
1.9 kW
120 VAC, 24 A
2.8 kW
208 VAC, 24 A
4.9 kW
Three-Phase Input; UL-Listed
120/208 VAC, 24 A
8.6 kW
120/208 VAC, 40 A
14.4 kW
120/208 VAC, 48 A
240/415 VAC, 24 A
17.2 kW
Input Wiring Options
10-ft (3-m) non-detachable power supply cord.
Hard-wired terminal block for connection of field wiring
Receptacle Options
NEMA 5-20; IEC 320C13; IEC 320C19
Maximum Number of Receptacles
48
12
24
Maximum Power Consumption
6 W
Measurement Accuracy
Voltage - +/- 1% +0.1 VAC
Current - +/- 1.5% +0.01 A from 1 % to 10 % of unit rating
+/- 1% +0.01 A from >10% to 125% of unit rating
Insulation
Class I reinforced SELV
Dielectric Electric Strength
Tested up to 4242 VDC
Overcurrent Protection
UL489-Listed, CSA, TUV, CCC hydraulic-magnetic circuit breaker, 20 A, 5000 A, A.I.C
Operating Temperature Range
32 A or less input models: 41° F to 140° F (5° C to 60° C)
40 A and 48 A input models without case ventilation: 41° F to 122° F (5° C to 50° C)
40 A and 48 A input models with case ventilation: 41° F to 140° F (5° C to 60° C)
Storage Temperature Range
-4° F to 185° F (-20° C to 85° C)
Humidity %
10% to 90% non-condensing
Altitude ft (m)
6562 ft (2000 m)
Mounting
Factory-installed tool-less
brackets
Universal mounting bracket
Factory installed, right-angle mounting brackets
Width x Depth Inches (mm)
Low-profile: 2.2 x 1.96 (56 x 50)
Standard: 2.2 x 2.7 (56 x 69)
1.73 x 9.84 (44 x 250)
3.46 x 9.84 (88 x 250)
Table A.1 MPH2 Rack PDU Specifications
Vertiv
| Vertiv™ MPH2 Rack PDU Installer/User Guide
39
Summary of Contents for MPH2
Page 1: ...Vertiv MPH2 Rack PDU Installer User Guide ...
Page 16: ...Vertiv Vertiv MPH2 Rack PDU Installer User Guide 12 This page intentionally left blank ...
Page 42: ...Vertiv Vertiv MPH2 Rack PDU Installer User Guide 38 This page intentionally left blank ...
Page 48: ...Vertiv Vertiv MPH2 Rack PDU Installer User Guide 44 This page intentionally left blank ...
Page 49: ......