Rubber Hose Connection Volumes
One-inch diameter rubber hose connections are field provided. The fluid volume is total for supply and return hoses of equal
length (two hoses).
Fluid Volume
Length of Kit Hoses, ft (m)
cubic in.
gal, (l)
5 (1.5)
94.34
0.41 (1.7)
10 (3)
188.59
0.82 (3.2)
15 (4.5)
282.84
1.23 (4.8)
20 (6)
377.09
1.64 (6.3)
25 (7.5)
471.34
2.04 (8)
Table 6.4 Fluid Volume of Rubber Hose Connection Sets
Field Piping Connection Volumes
Field supplied, field installed piping (PVC, copper, etc.) depends on pipe diameter and length. Table 6.5 below, describes
the typical fluid volumes depending on pipe diameter.
Line Size, O.D., in.
Fluid Volume
gal/ft
l/m
1-1/8
0.043
0.532
1-3/8
0.065
0.811
1-5/8
0.092
1.148
Table 6.5 Piping Fluid Volume Gallon per Foot (Liter per Meter) Reference Type L
Copper
6.2 Water Quality Requirements
To safeguard the maximum lifetime of air/water heat exchangers, the water used for cooling purposes must meet the VGB
Cooling Water Guidelines (VGB-R 455 P). The cooling water used must be soft enough to prevent deposits, but it must not
be too soft because that would lead to corrosion of the heat exchanger.
Table 6.6 on the facing page, lists the most important impurities and measures for their removal.
Vertiv | XDU™ Liquid to Air Heat Exchanger for Chip Cooling
26
Summary of Contents for Liebert XDU 060
Page 1: ...Liebert XDU Liquid to Air Heat Exchanger for Chip Cooling Installer User Guide 600 mm Wide ...
Page 10: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 6 This page intentionally left blank ...
Page 38: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 34 ...
Page 74: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling ...