Symptom
Possible Cause
Check or Remedy
Local display is not operational, but unit
operates
Local display cable disconnected
Connect cable.
Local display cable damaged
Replace cable.
Local display configuration lost
Contact Vertiv Technical Support.
Local display is not operational, and unit
does not operate
Unit electrical supply is Off
Restore electrical supply.
Unit main switch is Off
Switch On the unit.
Control board supply issue
Contact Vertiv Technical Support.
Control board issue
Contact Vertiv Technical Support.
Main 24 VAC fuse trips
Shorts or loose connections
Check the wiring connections of the 24 VAC circuit.
Faulty circuit board
Replace the circuit board.
XDU™ Liquid to Air Heat Exchanger for Chip
Cooling not making capacity
Air in the system
Check for adequate charge in system, see
page 30. Purge air from the high-point vent on the top of the unit
Entering air temperature too high
Reduce entering air temperature.
Table 9.1 Unit Diagnostics (continued)
Vertiv | XDU™ Liquid to Air Heat Exchanger for Chip Cooling
40