Fans
1.
Ensure mounting bolts are tight.
2.
Verify fan guard bolts are tight.
3.
Make sure Impeller spins freely.
4. Verify fan safety switch (door switch).
5.
Check fan amp draw.
#1
L1
L2
L3
#2
L1
L2
L3
Other
1.
Verify expansion tank air pressure is above 10 psi.
2.
Verify proper water maintenance is being performed.
3.
Check for water leaks.
4. Compare pump and fan amps to nameplate amps.
Vertiv | XDU™ Liquid to Air Heat Exchanger for Chip Cooling
50