Vertiv | Liebert
®
NXL
™
500-750kVA UPS Installation Manual |
61
Notes on Tables
1.
Nominal input current (considered continuous) is based on full-rated output load. Maximum current
includes nominal input current and maximum battery recharge current (considered noncontinuous).
Continuous and noncontinuous current are defined in NEC 100.
2.
Maximum input current is controlled by the current limit setting, which is adjustable. Values shown are for
maximum current limit. If a smaller input feed breaker is used, the input current limit can be adjusted.
Contact your Vertiv representative for more information.
3.
The Rectifier Input Feed Breaker must be set to handle the
®
NXL transformer inrush of up to eight times
the nominal current.
4.
For breaker coordination while the module is overloaded, see the current-versus-time values on the
overload curves in
and
.
5.
Nominal battery voltage is shown at 2V/cell.
Table 15
Current ratings—bypass input
UPS Rating
Voltage
VAC
Nominal
Current
kVA
kW
500
450
480
601
625
562.5
480
752
750
675
480
902
750
675
575
753
750
675
600
722
Table 16
Current ratings—output
UPS Rating
Voltage
VAC
Nominal
Current
kVA
kW
500
450
480
601
625
562.5
480
752
750
675
480
902
750
675
575
753
750
675
600
722
Table 17
Current ratings—battery
UPS Rating
Voltage
VAC
Nominal
VDC
Maximum Battery
Current at EOD
kVA
kW
500
450
480
480
1241
625
562.5
480
480
1530
750
675
480
480
1845
750
675
575
480
1851
750
675
600
480
1845