Vertiv | Liebert
®
NXL
™
500-750kVA UPS Installation Manual |
47
Figure 34 Output terminal detail, 625/750kVA Liebert
®
NXL
™
, N+1 multi-module unit without static bypass,
cont’d
NOTES:
1. All dimensions are in inches (mm)
2. Control wiring and power wiring must be run in separate conduits.
3. Unless otherwise noted, use copper or aluminum conductors suitable
for at least 75°C.
4. All wiring is to be in accordance with national and local electrical
codes.
Neutral
Output
Ground
Output
Phases
RIGHT SIDE (OUTPUT)
RIGHT FRONT
A
B
C
OUTPUT GROUND
O
1.57 (40) Typ.
1.38 X .56 Slot
10 Places
NEUTRAL
O
1.38 x .5
Slot 5
Places Each
Busbar
OUTPUT
PHASES
O
1.75
(44) Typ.
(Top Entry)
1.75 (44)
Typ.
(Bottom
Entry)
1.75 (44)
Typ.
(Bottom
Entry)
1.75 (44)
Typ.
1.75 (44)
Typ. (Top
Entry)
.56 (14)
Typ. 5
Places
.56 (14)
Typ. 5
Places
.56 (14)
Typ. 20
Places
0
32.0
(813)
39.4
(1002)
53.2
(1352)
76.8
(1950)
DO NOT DOUBLE-STACK LUGS
CB1-3
CB1-3