Vertiv
| Liebert
®
NXL
™
500-750kVA UPS Installation Manual |
36
Figure 24 Field connections, shipping split 500kVA Liebert
®
NXL
™
, multi-module or SMS with static bypass,
Page 1
WH P/N
START
(Part B- Inverter Cabinet)
FINISH
(Part A- Rectifier Cabinet)
Label
604309G
1
02-806704 Inverter Gate Drive A
UPSC
To: 02-806701
ID: P0400A
604309G
2
02-806704 Inverter Gate Drive B
UPSC
To: 02-806701
ID: P0400B
604309G
3
02-806704 Inverter Gate Drive C
UPSC
To: 02-806701
ID: P0400C
604325G1
DCFAN_2 & DCFAP_1 DC Fuse Block
02-806708
External Interface Board
To: 02-806708
ID: P0814
M10 FLAT WASHER
M10 RIBBED WASHER(x2)
M10 HEX HEAD BOLT
(+)DC BUSBAR
(-)DC BUSBAR
DETAIL A
M10 NUT HEX
PART A - WIRE STARTING POINT
PART B - WIRE FINISHING POINT
DC POWER CONNECTION BETWEEN PART A AND B.
604309G1
604309G2
604309G3
604325G1
02-806704-PHASE A
02-806704-PHASE B
02-806704-PHASE C
DETAIL A
HARDWARE PROVIDED WITH PART B.
(4) BOLTS TOTAL.
TORQUE CONNECTION TO 27 N-M, 240 IN-LBS.