Vertiv | Liebert
®
NXL
™
500-750kVA UPS Installation Manual |
37
Figure 25 Field connections, shipping split 500kVA Liebert
®
NXL
™
, multi-module or SMS with static bypass,
Page 2
DC POWER CONNECTION BETWEEN PART B AND A.
HARDWARE PROVIDED WITH PART A.
(4) BOLTS TOTAL.
TORQUE CONNECTION TO 27 N-M, 240 IN-LB.
M10 NUT HEX
M10 RIBBED
WASHER(x2)
M10 FLAT WASHER
M10 HEX HEAD BOLT
DETAIL B
LOOSEN HARDWARE TO ALLOW
BUSBAR TO MOVE TO JOIN TO
PART B BUSBAR.
RETIGHTEN AND TORQUE TO
27 Nm(240 in-lb)
604308G1
604313G1
604348G1
604352G1
604313G2
604307G1
604348G1
604348G1
604349G1
604348G1
604348G1
(+) DC BUSBAR
(-) DC BUSBAR
DETAIL B
PART A - WIRE FINISHING POINT
PART B - WIRE STARTING POINT