Vertiv | Liebert
®
NXL
™
500-750kVA UPS Installation Manual |
51
Figure 38 Shipping Split, 625/750kVA Liebert
®
NXL
™
, SMS and 1+N multi-module unit with static bypass
P
A
R
T
A
- WIRE ST
AR
TING POINT
P
AR
T
B - WIRE FINISHING POINT
Hardware Provided With Part B.
(4) Bolts
T
o
tal.
T
o
rque Connection to 27 N-m (240 in-lb).
M10 FLA
T
W
ASHER
M10 RIBBED W
ASHER (x2)
M10 HEX HEAD BOL
T
Low V
oltage Wire Connections Between Parts
A
and B
Wires are coiled and tied in Part
A.
Uncoil, route and connect wires in finish part as shown.
Use wire label as guide for “T
O” component, connection ID and wire part number
.
T
ie wires away from sharp edges, busbar and electronic components.
DC Power Connection Between Parts
A
and B
(+) DC BUSBAR
LOOSEN HARDW
ARE
T
O
ALLOW
BUSBAR T
O
MOVE T
O
JOIN T
O
P
A
R
T
B BUSBAR.
RETIGHTEN
AND T
O
RQUE T
O
27 N-m (240 in-lb)
02-806704-
PHASE A
02-806704-
PHASE B
02-806704-
PHASE C
02-806707-
02-806705-
02-806716-
F42 & F43
(-) DC BUSBAR
531988G2
531985G1
531983G1
531985G2
531984G1
531985G3
531988G1
532061G1
532062G1
Detail A
DET
A
IL
A