Vertiv | Liebert
®
NXL
™
500-750kVA UPS Installation Manual |
41
Figure 28 Outline drawing, 625/750kVA Liebert
®
NXL
™
, N+1 multi-module unit without static bypass
NOTES
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit required for air exhaust
and maintenance.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable
access plates.
Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Depth dimension includes front door and rear panel.
7. Width dimensions include side panels. Subtract 1.4" (35mm) when
removing both side panels.
Rectifier / DC
Cable Entry
Control Cable
Entry \ Exit
Bypass \ Output
Cable Exit
Rectifier / DC
Cable Entry
Control Cable
Entry / Exit
Outer Edge
Corner Post
Front Most
Edge Of Frame
Bypass \ Output
Cable Exit.
Rectifier
Center of
Inverter
71.6
[1819]
62.4
[1585]
62.4
[1585]
Inverter Split (Part B)
15.8
[402]
3.7
[94]
17.6
[447]
.0
( 0 )
.0
( 0 )
3.3
[85]
14.8
[376]
2.1
[53]
19.1
[486]
24.6
[626]
15.2
[385]
4.1
[105]
.0
( 0 )
0
.6
[15]
Panel Width
76.8
[1950]
14.4
[367]
11.6
[294]
109.9 (2791)
10.6
[269]
1.6
[40]
17.7
[449]
23.6
[600]
12.3
[312]
24.6
[625]
31.5
[800]
36.3
[922]
26.0
[660]
31.5
[800]
23.8
[605]
Section A-A
Bottom View
B
Detail B
A
A
Gravity
Center of
Gravity
125 (3175)
39.4 (1000)
Right Side View
Left Side View
Top View
Front View
Rectifier Split (Part A)
16.6
[423]