12.2 Checklist for Setting up the Device
Performed checks
Done
(to be signed upon
completion)
Remarks
Check device for damage upon receipt.
Check the ground for being horizontal.
Check bearing capacity of ground.
Add-on and align, connect to server cabinet, position feet of
the rack and adjust them horizontally
Cables connected with server cabinet:
Temperature sensors (optional)
Server shut-down (optional)
Door contact (optional)
Unit connected with set of external valves (optional):
- Valve drive
- Flow meter with temperature sensors (optional)
Optional automatic door opening adjusted at server cabinet
No remainders of packaging inside DCD
All assembly tools removed
Bushings into the device proper and air-tight
Chilled water connection leak-proof / pressure-tested
Chilled water system de - aerated
Volume flow of chilled water adjusted
Condensed water line unobstructed
Smell trap of chilled water system functional
Condensate tray connected to condensed water line
All front panels closed (air ducts technically separated)
.............................................
........................................
......................................