3.7 Mechanical Requirement
3.7.1 Composition
The UPS single switch contains the cabinet of 600 mm width, which provides the maintenance bypass switch Q3.
The UPS four switches contains the cabinet of 1200 mm width, which provides the rectifier input switch Q1, bypass input
switch Q2, maintenance switch Q3, and output switch Q5.
3.7.2 Moving Cabinet
W A R N IN G !
1. T h e liftin g equ ipm en t fo r m o vin g th e UP S cabin et m u st h ave en o u gh lift capacity.
2. T h e cen ter o f gravity o f th e UP S cabin et is h igh ; avo id fallin g o ver du rin g th e cabin et
m o vem en t.
3. Vertical h an gin g o f cabin et is n o t allo wed.
Ensure that the weight of the UPS does not exceed the capacity of the lifting equipment. For the UPS weight, refer to Table
12.3 on page 172.
The UPS cabinet can be moved by forklift or other similar lifting equipment.
3.7.3 Clearance
Because the UPS has no perforated doors at the two sides, there is no special clearance requirement on the two sides.
Besides the local regulations, to enable routine tightening of the power terminals within the UPS, it is recommended that
clearance around the front of the UPS should be larger than 1200 mm and enough to enable free passage of personnel with
the door fully open. Meanwhile, maintain at the back of the cabinet a clearance at least 500 mm to permit adequate
circulation of air coming out of the UPS.
3.7.4 Cable Access Mode
For single switch UPS, only top cable entry arrangement is possible.
For the UPS with four switches, both top and bottom entry arrangement can be possible.
For further description, refer to Power Cable Connection Steps and Signal Cable Connection Steps.
3 Mechanical Installation
34
Vertiv™ Liebert® APM Plus User Manual
Summary of Contents for APM Plus 0500kMK16FN02000
Page 1: ...Vertiv Liebert APM Plus User Manual 50 500 kVA UPS...
Page 8: ...vi This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 34: ...2 Overview 26 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 45: ...Four switches 500 kVA 3 Mechanical Installation 37 Vertiv Liebert APM Plus User Manual...
Page 76: ...Figure 5 11 Customize the display 5 Touch Screen 68 Vertiv Liebert APM Plus User Manual...
Page 86: ...Figure 5 20 Enable module redundancy 5 Touch Screen 78 Vertiv Liebert APM Plus User Manual...
Page 91: ...Figure 5 24 Status Gauge setting options 5 Touch Screen 83 Vertiv Liebert APM Plus User Manual...
Page 92: ...5 Touch Screen 84 Vertiv Liebert APM Plus User Manual...
Page 94: ...5 Touch Screen 86 Vertiv Liebert APM Plus User Manual...
Page 95: ...Figure 5 26 Unit status Bypass details 5 Touch Screen 87 Vertiv Liebert APM Plus User Manual...
Page 96: ...Figure 5 27 Unit status Battery details 5 Touch Screen 88 Vertiv Liebert APM Plus User Manual...
Page 97: ...Figure 5 28 Unit status Load details 5 Touch Screen 89 Vertiv Liebert APM Plus User Manual...
Page 100: ...5 Touch Screen 92 Vertiv Liebert APM Plus User Manual...
Page 112: ...5 Touch Screen 104 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 184: ...12 Specifications 176 This page intentionally left blank Vertiv Liebert APM Plus User Manual...