590-2112-501A/SL-29427/4200-117
3-7
Revision 3
If JP1 is not installed, the alarm LED and alarm relay on the ELSi interface module will remain on
when the electrolyte level is returned to normal. To reset the alarm, press the reset button on
the side of the ELSi interface module. See Figure 9.
8.
After completing the test, turn
Off
then
On
the power to all the sensors, which allows each
sensor to leave test mode and enter into normal mode of operation.
3.6
Troubleshooting
If the ELS sensor module does not activate an alarm when the electrolyte level is lowered, there could
be air bubbles in the adhesive applied in-between the ELS sensor module and the battery. To confirm
this, remove the ELS sensor module from the battery, remove any residue of adhesive from the battery
case and sensor and reapply new adhesive. After the new adhesive is installed, double check that the
electrolyte level is at the proper level and recalibrate the ELS sensor module.
Note
: Alarms on all ELS sensor modules must be cleared before you can reset the system alarm on the
ELSi interface module.