590-2112-501A/SL-29427/4200-117
3-2
Revision 3
Figure 3 - ELSi Interface Module Alarm Contacts Jack
3.2
Mounting the ELS Sensor on the Battery Case
Use the ELS sensor module “
LOW LEVEL TRIGGER
” graphic on the label to position and mount the ELS
sensor module even with the low electrolyte level line on the battery case. To attach the ELS sensor
modules to the batteries, use a small amount of the provided adhesive and a thin strip of 3m gel tape as
a temporary support to mount the ELS sensor modules to the side of the batteries.
Figure 4 - Positioning the ELS Sensor Module on Battery Case
1.
For mounting the ELS sensor, follow these steps:
Verify the electrolyte level in the battery is over the middle level between the low and high-level
lines. If the electrolyte is below the average level, add more distilled water.
2.
Clean battery case surface where sensor will be mounted.
a.
Remove moisture, dirt, oil, grease and dust using baking soda and water.
b.
Remove any excess baking soda and water using a rubbing alcohol and wipe it dry.
3.
Clean the surface of the ELS module with rubbing alcohol and wipe dry.