Vertiv™ NetSure™ 512
NGBB
-48 VDC Power System User Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
35
11.
Reconnect the external wiring to the correct terminals on the customer connection terminal block. First remove the electrical
tape that was applied to the bare wire end in a previous step. DO NOT allow the bare wire end to contact any grounded or
energized object. After securing the wire, gently tug on the wire to ensure that it cannot be pulled out of the terminal block.
Repeat for each wire to be reconnected.
12.
Remove the grounding wrist strap.
13.
Enable the external alarms, or notify appropriate personnel that this procedure is finished.
14.
Ensure that there are no local or remote alarms active on the system.