EXS
User Manual 10H52260UM60 - Rev. 1 - 10/2017
31
output copper shorting bars (oA-oB-oC), oN and the load. Refer to Table 3-1 for the tightening torque values. Make
sure that the phase rotation is correct.
Warning
Prior to the service engineer's visit, if the load is not ready to be connected to the power supply, it is important to ensure the
terminals of the output cables are insulated safely
Connecting the batteries
If the external battery is required, ensure correct polarity between the battery string terminals and the
circuit
breaker
, and between the
circuit breaker
and the UPS cabinet battery input terminals (Bat+, N, Bat-), i.e. (Bat
+) to (+), (Bat-) to (-) and (N) to (N).
This completes the connection procedure. At this point it is possible to replace the protective covers.
Note
After connection, take appropriate measures to seal the cable entry holes.
3.2
Wiring the Signal Cables
Overview
Depending on the specific on-site needs, the UPS requires auxiliary connections to manage the battery system
(including the external battery circuit breaker), communicate with a PC, provide alarm signals for external devices,
enable a remote EPO and/or the bypass back feed circuit breaker signal, and for parallel communication functions.
These functions are performed by the communication box in the UPS cabinet. As shown in Figure 3-6, the
communication box provides the following ports:
Figure 3-6 Illustration drawing of communication box ports
1. Intellislot port
2. Dry contact port
3. RS232 port
4. Ethernet port (not used)
5. Parallel/LBS port
6. REPO port
7. USB port
8. Multifunctional port