![Vertiv 0015kTH1AFN02 User Manual Download Page 105](http://html1.mh-extra.com/html/vertiv/0015kth1afn02/0015kth1afn02_user-manual_1008194105.webp)
EXS
104
User Manual 10H52260UM60 - Rev. 1 - 10/2017
Menu
Item
Setting range
Default setting
Battery test weekday
Sunday, Monday, Tuesday,
Wednesday, Thursday, Friday,
Saturday
Wednesday
Battery test time
HH:MM:SS
0:00:00
Battery series
24, 32, 40
32
Discharge protect time
1
~
4320 (min)
4320
Equal charge enable
YES, NO
NO
Temperature compensation
Enable, Disable
Disable
Replace battery
Button
Button
Outlet
Turn on outlet
Appear only when outlet
off
Turn off outlet
Appear only when outlet
on
Reboot outlet
Appear only when outlet
on
Turn off when UPS overload on
battery
YES, NO
NO
Turn off when UPS on battery
for
0
~
4320 (min)
2
Turn off when backup time less
than
0
~
4320 (min)
0
Turn off when battery capacity
less than
20
~
80%
30%
Turn on when power returns
for
0
~
4320 (min)
0
Monitor
Language
English,
Chinese
English
Date
YYYY-MM-DD
2016-10-01
Time
HH:MM:SS
00:00:00
Display orientation
Auto-rotate, Horizontal, Vertical
Auto-rotate
Audible alarm
Enable, Disable
Enable
Control port protocol
Modbus, Sensor
Sensor
Modbus address
1
~
128
1
IPv4 address
ddd.ddd.ddd.ddd (where 'd' is a
decimal number)
192.168.1.10
Subnet mask
255.255.255.0
Gateway address
192.168.1.1
Change settings password
The password may be a numerical
value only and include any
character between 0 and 9. The
password length is 6 characters
111111